Manufacturer
Dwyer Instruments
Type
Carbon Dioxide/Volatile Organic Compound Transmitter
Range
CO2: 0 to 2000 or 0 to 5000 ppm (depending on model)
VOC: 0 to 2000 ppm CO2 equivalent
Accuracy
CO2: ±40 ppm ±3% of reading
Temperature
Dependence: ±8 ppm / °C at 1100 ppm
Non Linearity
CO2: 16 ppm
PRESSURE
Dependence: CO2: 0.13% of reading per mm of Hg
Response Time
CO2: 2 minutes for 99% step change; VOC: 5 minutes
Maximum operating temperature
32 to 122°F (0 to 50°C)
Range
Duct Air Velocity: 0-4000 FPM (20.32 m/s)
Accuracy
16 to 35 VDC / 19 to 28 VAC
Power
Average: 2 watts
Peak: 3.75 watts
POWER CONSUMPTION
CO2: Single-beam, dual-wavelength NDIR; VOC: MEMS metal oxide semiconductor
Output
Current: 0 to 20 mA, 4 to 20 mA, 0 to 10 mA, or 2 to 10 mA (depending on selection jumper, max 500 O)
Voltage: 0 to 10 VDC, 2 to 10 VDC, 0 to 5 VDC, or 1 to 5 VDC (depending on selection jumper, min 500 O)
Relay: SPST NO 2A @ 30 VDC
Enclosure Rating
Duct mount: NEMA 4X (IP66) for housing only
Wall mount: IP20